Mejores selecciones
Siemens Disyuntor 3RV2032-4UA10
$ 630 .96
(5) 1
Comentarios
Cantidad
MOQ : 1
Pagos
Parámetro
Tipo | 3RV2 |
Tipo de disyuntor | Motor Protection Circuit Breakers |
Corriente nominal | 40 |
Número de polos | 1 pole |
Rango de ajuste para disparadores de sobrecarga térmica | 32...40 A |
¡El Siemens Circuit Breaker es de alta calidad!
Circuit breaker size S2 for motor protection, CLASS 10 A-release
32...40 A N-release 585 A screw terminal increased switching
capacity
product brand name SIRIUS
product designation Circuit breaker
design of the product For motor protection
product type designation 3RV2
General technical data
size of the circuit-breaker S2
size of contactor can be combined company-specific S2
product extension
auxiliary switch Yes
power loss W for rated value of the current
at AC in hot operating state 20?W
at AC in hot operating state per pole 6.7?W
insulation voltage with degree of pollution 3 at AC
rated value
690?V
surge voltage resistance rated value 6?kV
maximum permissible voltage for safe isolation
in networks with grounded star point between
main and auxiliary circuit
400?V
protection class IP
on the front IP20
of the terminal IP00
shock resistance
acc. to IEC 60068-2-27 25g / 11 ms Sinus
mechanical service life (switching cycles)
of the main contacts typical 50?000
of auxiliary contacts typical 50?000
electrical endurance (switching cycles)
typical 50?000
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
reference code acc. to DIN EN 81346-2 Q
Ambient conditions
installation altitude at height above sea level
maximum
2?000?m
ambient temperature
during operation -20?...?+60?degrees centigrade
during storage -50?...?+80?degrees centigrade
during transport -50?...?+80?degrees centigrade
temperature compensation -20?...?+60?degrees centigrade
relative humidity during operation 10?...?95?%
Main circuit
number of poles for main current circuit 3
adjustable pick-up value current of the currentdependent overload release
32?...?40?A
operating voltage
rated value 690?V
at AC-3 rated value maximum 690?V
operating frequency rated value 50?...?60?Hz
operating current rated value 40?A
operating current
at AC-3
at 400 V rated value 40?A
operating power
at AC-3
at 230 V rated value 11?000?W
at 400 V rated value 18?500?W
at 500 V rated value 22?000?W
at 690 V rated value 37?000?W
operating frequency
at AC-3 maximum 15?1/h
Protective and monitoring functions
product function
ground fault detection No
phase failure detection Yes
trip class CLASS 10
design of the overload release thermal
operational short-circuit current breaking capacity
(Ics) at AC
at 240 V rated value 100?kA
at 400 V rated value 50?kA
at 500 V rated value 8?kA
at 690 V rated value 4?kA
maximum short-circuit current breaking capacity (Icu)
at AC at 240 V rated value 100?kA
at AC at 400 V rated value 100?kA
at AC at 500 V rated value 15?kA
at AC at 690 V rated value 6?kA
response value current
of instantaneous short-circuit trip unit 585?A
UL/CSA ratings
full-load current (FLA) for three-phase AC motor
at 480 V rated value 40?A
at 600 V rated value 40?A
yielded mechanical performance hp
for single-phase AC motor
at 110/120 V rated value 3?hp
at 230 V rated value 7.5?hp
for three-phase AC motor
at 200/208 V rated value 15?hp
at 220/230 V rated value 15?hp
at 460/480 V rated value 30?hp
at 575/600 V rated value 40?hp
Short-circuit protection
product function short circuit protection Yes
design of the short-circuit trip magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
at 240 V none required
at 400 V 125
at 500 V 100
at 690 V 80
Installation/ mounting/ dimensions
mounting position any
mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height 140?mm
width 55?mm
depth 149?mm
Circuit breaker size S2 for motor protection, CLASS 10 A-release
32...40 A N-release 585 A screw terminal increased switching
capacity
product brand name SIRIUS
product designation Circuit breaker
design of the product For motor protection
product type designation 3RV2
General technical data
size of the circuit-breaker S2
size of contactor can be combined company-specific S2
product extension
auxiliary switch Yes
power loss W for rated value of the current
at AC in hot operating state 20?W
at AC in hot operating state per pole 6.7?W
insulation voltage with degree of pollution 3 at AC
rated value
690?V
surge voltage resistance rated value 6?kV
maximum permissible voltage for safe isolation
in networks with grounded star point between
main and auxiliary circuit
400?V
protection class IP
on the front IP20
of the terminal IP00
shock resistance
acc. to IEC 60068-2-27 25g / 11 ms Sinus
mechanical service life (switching cycles)
of the main contacts typical 50?000
of auxiliary contacts typical 50?000
electrical endurance (switching cycles)
typical 50?000
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
reference code acc. to DIN EN 81346-2 Q
Ambient conditions
installation altitude at height above sea level
maximum
2?000?m
ambient temperature
during operation -20?...?+60?degrees centigrade
during storage -50?...?+80?degrees centigrade
during transport -50?...?+80?degrees centigrade
temperature compensation -20?...?+60?degrees centigrade
relative humidity during operation 10?...?95?%
Main circuit
number of poles for main current circuit 3
adjustable pick-up value current of the currentdependent overload release
32?...?40?A
operating voltage
rated value 690?V
at AC-3 rated value maximum 690?V
operating frequency rated value 50?...?60?Hz
operating current rated value 40?A
operating current
at AC-3
at 400 V rated value 40?A
operating power
at AC-3
at 230 V rated value 11?000?W
at 400 V rated value 18?500?W
at 500 V rated value 22?000?W
at 690 V rated value 37?000?W
operating frequency
at AC-3 maximum 15?1/h
Protective and monitoring functions
product function
ground fault detection No
phase failure detection Yes
trip class CLASS 10
design of the overload release thermal
operational short-circuit current breaking capacity
(Ics) at AC
at 240 V rated value 100?kA
at 400 V rated value 50?kA
at 500 V rated value 8?kA
at 690 V rated value 4?kA
maximum short-circuit current breaking capacity (Icu)
at AC at 240 V rated value 100?kA
at AC at 400 V rated value 100?kA
at AC at 500 V rated value 15?kA
at AC at 690 V rated value 6?kA
response value current
of instantaneous short-circuit trip unit 585?A
UL/CSA ratings
full-load current (FLA) for three-phase AC motor
at 480 V rated value 40?A
at 600 V rated value 40?A
yielded mechanical performance hp
for single-phase AC motor
at 110/120 V rated value 3?hp
at 230 V rated value 7.5?hp
for three-phase AC motor
at 200/208 V rated value 15?hp
at 220/230 V rated value 15?hp
at 460/480 V rated value 30?hp
at 575/600 V rated value 40?hp
Short-circuit protection
product function short circuit protection Yes
design of the short-circuit trip magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
at 240 V none required
at 400 V 125
at 500 V 100
at 690 V 80
Installation/ mounting/ dimensions
mounting position any
mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height 140?mm
width 55?mm
depth 149?mm
Las personas que compraron este artículo también vieron
Siemens Disyuntor 3RV2011-1AA10
US$219.13
Mitsubishi Disyuntor NF630-SEW 4P
US$962.11
Siemens Disyuntor 5SJ6220-7CC20
US$31.25
CHINT Transformador BKC-300
US$105.00
Fuji Contactor SC-E7M8-C
US$244.23
Ferraz Shawmut Fusible DN00UB69V125L
US$50.00
ABB Relé CR-M110AC4G
US$17.69
UniOhm Resistor 0402WGJ0112TCE
US$4.81
Los clientes ven con frecuencia
Carel Válvula de expansión E6VB2ASV00
US$839.00
Mitsubishi Compresor RE277NRAMT
US$389.00
Togami Contactor CLK-25J3
US$79.00
OEG Relé PCE-124D1H
US$1.15
Publicaciones relacionadas recientes
-
01/08/2024
¿Por qué vibra el servomotor?
¿En qué casos vibrará un servomotor? ¿Qué pasa si el servomotor vibra? ¿Cómo podemos solucionar los problemas causados por la vibración? Este artículo explicará varias razones para esto.
-
03/10/2024
Todo lo que debe saber sobre el embrague magnético del compresor de CA del coche
Este artículo presenta los componentes del embrague magnético del compresor y su principio de funcionamiento, así como varios parámetros importantes. Además, también le brindamos algunas experiencias sobre cómo lidiar con la quema de los embragues del compresor del aire acondicionado.
-
08/04/2023
Aire acondicionado Mitsubishi vs Panasonic
El verano es tan difícil de pasar que las personas sin aire acondicionado son como peces fuera del agua. Es fundamental elegir un buen aire acondicionado.
-
12/05/2023
Principios y diferencias de los transmisores de 2, 3 y 4 hilos
Los transmisores de 2, 3 y 4 hilos se refieren a transmisores cuyas salidas son señales analógicas de corriente CC.
-
05/19/2022
17 fabricantes de compresores centrífugos, en el mundo. ¿cuántos conoce?
En la última década, en un contexto de globalización económica y feroz competencia, la industria de fabricación de compresores centrífugos también ha experimentado continuas fusiones, adquisiciones y reorganizaciones.
-
11/18/2023
Transmisores Rosemount Series 1151, 2088, 2051, 3051CA, 3051S y sus diferencias
El transmisor de presión Rosemount es un tipo de transmisor de presión general. Está fabricado según la ley de inducción electromagnética y la norma JB/T9248-1999.
-
08/08/2023
Método de cálculo del peso por metro de tubo de cobre para aire acondicionado
Método de cálculo del peso por metro de tubería de cobre para aire acondicionado.
-
02/17/2024
Método de cableado del relé PTC de nevera
El relé PTC (coeficiente de temperatura positivo) está conectado directamente en serie con el devanado secundario (devanado de arranque) y en paralelo con el devanado principal del motor.
-
07/29/2023
Compresor Scroll Vs. Compresor rotativo para CA
El compresor scrollue inventado en 1905 por el francés Copeland. Creó la compañía Copeland en los Estados Unidos, donde se utilizan principalmente acondicionadores de aire de agua
-
06/27/2023
Principio de funcionamiento del compresor frigorífico, esquema eléctrico, estructura
El componente principal del refrigerador es el compresor. Si un frigorífico no está equipado con un compresor de buena calidad y tecnología no puede ser un buen frigorífico.