Chint Disyuntor NM8SL-100S/4A
No hay precio en este momento, puede solicitar una cotización
¡El Chint Circuit Breaker es de alta calidad!
¡El rated limit breaking capacity (kA) Icu AC50Hz 400V 50
¡El rated running breaking capacity (kA) Ics AC50Hz 400V 50
¡El minimum value of the rated residual switching-on and switching-off capacity I△m is 25%Icu. Twelve point five
Use category a.
Total life expectancy with load and no load 1500/8500/10000
Tripper type intelligent
¡El residual operating current (adjustable in the fourth gear) I △ n (a) x1: 0.05/0.1/0.2/0.5; X2:0.1/0.3/0.5/1
Breaking time (adjustable in third gear) Total breaking time (s) T1: 0.3/0.5/1
Weight (kg) 3P/4P 2.6/4
NM8 or NM8S plastic casing circuit breakers are NM8L and NM8SL residual current operated circuit breakers
after being assembled with residual current protection modules conveniently. NM8L and NM8SL series residual
current operated circuit breakers are mainly used in circuits with AC 50Hz, rated voltage up to 400V and
rated current up to 630A A.. Its main function is to provide indirect contact protection for fatal personal
electric shock, and at the same time, it can also be used to prevent electrical fire caused by ground fault
current. It can be used to protect the overload, short circuit and undervoltage of the line, and can also be
used for infrequent switching of the line.
NM8L: Thermomagnetic Residual Current Action Circuit Breaker
NM8SL: Intelligent Residual Current Action Circuit Breaker
Shell level 100A 250A 630A
¡El rated current (a) is 16, 20, 25, 32, 4050, 63, 80, 100, 125, 160, 180, 200, 225, 250, 315, 350, 400, 500, 630
Note: the maximum value of thermomagnetic residual current operated circuit breaker is 500A A.
3 means 3 poles
4 means 4 poles
4A indicates that the N pole is not equipped with an overcurrent release element, and the N pole is always on;
4B indicates that the N-pole is not equipped with an overcurrent release element, and the N-pole and the other
three poles are combined and divided together (the N-pole is combined first and then divided)
4C indicates that the N pole is equipped with an overcurrent trip element, and the N pole is closed and divided
together with the other three poles (the N pole is closed first and then divided), and the operating current is 1.0In;;
4D indicates that the N pole is equipped with an overcurrent tripping element, and the N pole is always on, and the
operating current is 1.0In;;
M: No code for motor protection: power distribution protection
Normal working conditions and installation conditions
¡El altitude of the product installation site is 2000m and below;
¡El external magnetic field of the installation site of residual current operated circuit breaker shall not
exceed 5 times of the earth magnetic field in any direction;
¡El action value of the intelligent release is not affected by temperature fluctuation. However, the maximum
allowable current of residual current operated circuit breaker is still the same as that of circuit breaker
Environmental temperature.
Damp-heat: the relative humidity of the atmosphere should not exceed 50% when the ambient air temperature is
+40℃, and it can be higher at lower temperature. ¡El monthly average maximum relative humidity in the wettest month is
90%, at the same time. ¡El monthly average minimum humidity in this month is +25℃, and the condensation on the
product surface due to temperature change is considered.
Pollution level: the pollution level is level 3
Characteristics
Using splicing modular design, users can install and maintain themselves without affecting the characteristics
of circuit breakers;
With power indication;
¡El residual action current and the breaking time of the residual current can be adjusted, which is convenient
for users to choose;
With residual current action indication and reset button, users can quickly judge the action reason of residual
current action circuit breaker.
In addition, the residual current operated circuit breaker cannot be closed without confirming and eliminating
the leakage fault (the reset button is not pressed);
¡El residual current operated circuit breaker equipped with auxiliary switch can remotely indicate the tripping
of the circuit breaker in case of leakage fault;
High breaking ability and no arcing;
With isolation function and reliable contact indication
Isolation position is in "0" (off) position;
Only when the contact is fully opened can the operating handle indicate the "0" (OFF) position;
Padlocks can only be installed when the contacts are opened;
Rotating the handle will not change the reliability of contact indication;
¡El isolation function shall ensure the mechanical reliability indicated by the contact, no residual current,
and the terminal on the power supply side can withstand high impact voltage;
Isolation function
¡El rated limit breaking capacity (kA) Icu AC50Hz 400V 50
¡El rated running breaking capacity (kA) Ics AC50Hz 400V 50
¡El minimum value of the rated residual switching-on and switching-off capacity I△m is 25%Icu. Twelve point five
Use category a.
Total life expectancy with load and no load 1500/8500/10000
Tripper type intelligent
¡El residual operating current (adjustable in the fourth gear) I △ n (a) x1: 0.05/0.1/0.2/0.5; X2:0.1/0.3/0.5/1
Breaking time (adjustable in third gear) Total breaking time (s) T1: 0.3/0.5/1
Weight (kg) 3P/4P 2.6/4
NM8 or NM8S plastic casing circuit breakers are NM8L and NM8SL residual current operated circuit breakers
after being assembled with residual current protection modules conveniently. NM8L and NM8SL series residual
current operated circuit breakers are mainly used in circuits with AC 50Hz, rated voltage up to 400V and
rated current up to 630A A.. Its main function is to provide indirect contact protection for fatal personal
electric shock, and at the same time, it can also be used to prevent electrical fire caused by ground fault
current. It can be used to protect the overload, short circuit and undervoltage of the line, and can also be
used for infrequent switching of the line.
NM8L: Thermomagnetic Residual Current Action Circuit Breaker
NM8SL: Intelligent Residual Current Action Circuit Breaker
Shell level 100A 250A 630A
¡El rated current (a) is 16, 20, 25, 32, 4050, 63, 80, 100, 125, 160, 180, 200, 225, 250, 315, 350, 400, 500, 630
Note: the maximum value of thermomagnetic residual current operated circuit breaker is 500A A.
3 means 3 poles
4 means 4 poles
4A indicates that the N pole is not equipped with an overcurrent release element, and the N pole is always on;
4B indicates that the N-pole is not equipped with an overcurrent release element, and the N-pole and the other
three poles are combined and divided together (the N-pole is combined first and then divided)
4C indicates that the N pole is equipped with an overcurrent trip element, and the N pole is closed and divided
together with the other three poles (the N pole is closed first and then divided), and the operating current is 1.0In;;
4D indicates that the N pole is equipped with an overcurrent tripping element, and the N pole is always on, and the
operating current is 1.0In;;
M: No code for motor protection: power distribution protection
Normal working conditions and installation conditions
¡El altitude of the product installation site is 2000m and below;
¡El external magnetic field of the installation site of residual current operated circuit breaker shall not
exceed 5 times of the earth magnetic field in any direction;
¡El action value of the intelligent release is not affected by temperature fluctuation. However, the maximum
allowable current of residual current operated circuit breaker is still the same as that of circuit breaker
Environmental temperature.
Damp-heat: the relative humidity of the atmosphere should not exceed 50% when the ambient air temperature is
+40℃, and it can be higher at lower temperature. ¡El monthly average maximum relative humidity in the wettest month is
90%, at the same time. ¡El monthly average minimum humidity in this month is +25℃, and the condensation on the
product surface due to temperature change is considered.
Pollution level: the pollution level is level 3
Characteristics
Using splicing modular design, users can install and maintain themselves without affecting the characteristics
of circuit breakers;
With power indication;
¡El residual action current and the breaking time of the residual current can be adjusted, which is convenient
for users to choose;
With residual current action indication and reset button, users can quickly judge the action reason of residual
current action circuit breaker.
In addition, the residual current operated circuit breaker cannot be closed without confirming and eliminating
the leakage fault (the reset button is not pressed);
¡El residual current operated circuit breaker equipped with auxiliary switch can remotely indicate the tripping
of the circuit breaker in case of leakage fault;
High breaking ability and no arcing;
With isolation function and reliable contact indication
Isolation position is in "0" (off) position;
Only when the contact is fully opened can the operating handle indicate the "0" (OFF) position;
Padlocks can only be installed when the contacts are opened;
Rotating the handle will not change the reliability of contact indication;
¡El isolation function shall ensure the mechanical reliability indicated by the contact, no residual current,
and the terminal on the power supply side can withstand high impact voltage;
Isolation function
Hacer preguntas
(0/1,200)
- Consulta: ¿Cómo puedo consultar la fecha de producción o fecha de vencimiento de un producto?
Responder: Para comprobar la fecha de producción o la fecha de caducidad de un producto, puede consultar el embalaje o las etiquetas del producto. Proporcionamos información clara y precisa sobre la fecha de fabricación y la fecha de vencimiento, lo que le permite tomar decisiones de compra informadas. Si necesita más ayuda, nuestro equipo de atención al cliente siempre está listo para ayudar.
- Consulta: ¿El producto tiene garantía de calidad?
Responder: ¡Absolutamente! Estamos orgullosos de ofrecer productos de alta calidad. Cada producto se somete a rigurosos controles de calidad para garantizar la excelencia y la satisfacción del cliente. Respaldamos la calidad de nuestros productos.
- Consulta: ¿Cómo puedo enviar comentarios o reseñar un producto?
Responder: Puede proporcionar comentarios o reseñar un producto accediendo a la página del producto y haciendo clic en la opción "Escribir una reseña" o "Dejar comentarios". Comparta su experiencia y opiniones para ayudar a otros compradores a tomar decisiones informadas.
Comentarios
- U
Usuario anónimo
25/11/2022
Chint Disyuntor NM8SL-100S/4A¡Todo estuvo bien! No hay problema alguno.ÚtilNo ayuda
Chint Disyuntor NM8SL-100S/4A
No hay precio en este momento, puede solicitar una cotización
Las personas que compraron este artículo también vieron
Schneider Disyuntor A9V53240
US$200.00
TRIAD Transformador F-22A
US$130.10
Delixi Contactor CJX2S-1210C
US$7.69
Siemens Fusible 5SB4 31
US$34.50
TYCO Relé V23054E 20B633
US$1165.00
EPCOS Resistor B72220Q421K101
US$1.92
Los clientes ven con frecuencia
Hitachi Compresor E405DHD-38A2YG
US$1125.00
SEALMASTER Cojinete FC-1510
Contacta con nosotros
NKK Interruptor HS16-2SN
US$48.30
TAKEX Sensor GMR2RPNN
US$138.00
Mitsubishi Compresor RB174GNKC
US$340.00
MGM Motor Eléctrico BM63C4
US$856.00
Schneider Arrancador suave ATS22C41Q
US$6297.31
HONGFA Relé HF33F-012-HT(335)
US$0.93
Yaskawa Servoaccionamiento SGDG-04GT400W
Contacta con nosotros
COSEL Fuente de alimentación COSELPAA100F
Contacta con nosotros
SICK Cortina de luz C4MT-10224ABB03FE0
US$2535.00
Sumitomo Reduction Drive Caja de cambios Reductor de velocidad CNH-6070-51
Contacta con nosotros
ATOS Válvula proporcional AGMZO-TERS-PS-10/315
Contacta con nosotros